N2XY power cables with cross-linked polyethylene (XLPE) insulation are designed for distribution and supply of electricity in low voltage installation systems. These cables feature copper conductors, XLPE insulation, and PVC sheathing, providing reliable performance for various industrial, commercial, and utility applications.

Technical Characteristics

Parameter Value
Rated Voltage (Uo/U) 600/1000 V
Test Voltage 4 kV
Conductor Operating Temperature +90°C (fixed installation)
Short Circuit Temperature +250°C (max. 5 seconds)
Installation Temperature Range -5°C to +50°C
Fixed Installation Temperature Range -20°C to +90°C
Minimum Bending Radius (Single Core) 15 × overall diameter
Minimum Bending Radius (Multi Core) 12 × overall diameter
Flame Resistance IEC 60332-1-2

Cable Construction

Component Material Details
Conductor Copper Class 1 solid or Class 2 stranded conductors according to BS EN 60228
Insulation XLPE Cross-linked polyethylene compound type DIX3
Bedding PVC Polyvinyl chloride filling
Sheath PVC Polyvinyl chloride compound type DMV6
Sheath Color Black Standard color, other colors available on request

Application Areas

These power and control cables are suitable for electricity supply in low voltage installation systems. They are well adapted for:

  • Underground installations in industrial applications (with additional mechanical protection)
  • Fixed installations on cable trays
  • Within conduits or fixed to walls
  • Power distribution in urban networks
  • Industrial plants and electrical power stations
  • Connection of control devices in industry and transportation systems

Core Identification

Configuration Core Colors
1 core Black
2 core Blue, Brown
3 core Brown, Black, Grey
3 core (with earth) Brown, Blue, Green/Yellow
4 core Blue, Brown, Black, Grey
4 core (with earth) Green/Yellow, Blue, Brown, Black
5 core Blue, Brown, Black, Grey, Black
5 core (with earth) Green/Yellow, Blue, Brown, Black, Grey
7 cores and higher Black cores with white numbering + Green/Yellow earth

Electrical and Dimensional Characteristics

Single Core Cables

Nominal Cross Section (mm²) Insulation Thickness (mm) Sheath Thickness (mm) Approx. Overall Diameter (mm) Approx. Weight (kg/km)
16 0.7 1.8 9.8 216
25 0.9 1.8 11.5 318
35 0.9 1.8 12.6 415
50 1.0 1.8 14.1 543
70 1.1 1.8 15.6 746
95 1.1 1.8 17.6 1000
120 1.2 1.8 19.2 1239
150 1.4 1.8 21.2 1515
185 1.6 1.8 23.1 1872
240 1.7 1.8 25.8 2403
300 1.8 1.8 27.8 2974
400 1.8 1.9 31.1 3834
500 1.8 2.0 34.9 4892
630 1.8 2.8 46.6 6544

Three Core Cables with Earth Conductor

Nominal Cross Section (mm²) Insulation Thickness (mm) Sheath Thickness (mm) Approx. Overall Diameter (mm) Approx. Weight (kg/km)
3×16/10 0.7/0.7 1.8 19.8 875.5
3×25/16 0.9/0.7 1.8 22.4 1223
3×35/16 0.9/0.7 1.8 24.3 1557
3×50/25 1.0/0.9 1.9 26.9 1863
3×70/35 1.1/0.9 2.0 30.0 2594
3×95/50 1.1/1.0 2.2 33.8 3505
3×120/70 1.2/1.1 2.3 37.0 4440
3×150/70 1.4/1.1 2.4 41.6 5333
3×185/95 1.6/1.1 2.6 45.8 6701
3×240/120 1.7/1.2 2.8 51.6 8674
3×300/150 1.8/1.4 3.0 67.2 10624

Four Core Cables

Nominal Cross Section (mm²) Insulation Thickness (mm) Sheath Thickness (mm) Approx. Overall Diameter (mm) Approx. Weight (kg/km)
4×1.5 0.7 1.8 11.3 188
4×2.5 0.7 1.8 12.2 240
4×4 0.7 1.8 13.3 314
4×6 0.7 1.8 14.5 408
4×10 0.7 1.8 17.1 615
4×16 0.7 1.8 19.6 885
4×25 0.9 1.8 23.7 1330
4×35 0.9 1.8 26.2 1758
4×50 1.0 2.0 27.1 2082
4×70 1.1 2.1 31.4 2937
4×95 1.1 2.2 35.0 3955
4×120 1.2 2.4 39.3 4979
4×150 1.4 2.6 43.6 6129
4×185 1.6 2.7 48.0 7591
4×240 1.7 2.9 53.9 9875
4×300 1.8 2.6 68.9 15124

Current Carrying Capacity

Single Core Cables (Amps at 30°C)

Nominal Cross Section (mm²) In Ground In Air (Flat) In Air (Trefoil)
16 115 131 112
25 148 177 145
35 177 217 174
50 209 265 206
70 256 336 254
95 307 415 305
120 349 485 348
150 393 557 392
185 445 646 444
240 517 774 517
300 663 901 585

Multi-core Cables (Amps at 30°C)

Nominal Cross Section (mm²) 2-4 Core Cables In Ground 2-4 Core Cables In Air
1.5 24 31
2.5 32 40
4 44 52
6 56 64
10 77 86
16 102 112
25 138 145
35 170 174
50 207 206

Derating Factors

For Ground Temperatures other than 20°C

Ground Temperature (°C) 10 15 20 25 30 35 40 45 50
Derating Factor 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76

For Air Temperatures other than 30°C

Air Temperature (°C) 20 25 30 35 40 45 50 55 60
Derating Factor 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71

The information contained in this document is for guidance only and is subject to change without notice or liability. All information is provided in good faith and is believed to be correct at the time of publication.

——Our Feature——

1.Imported equipment with experienced technical team
We have three plant and has 3048 employees which have 206 engineers. Plant has a series of imported production lines including Niehoff copper drawing lines, Troster Germany and Maillefer Finland 500KV VCV lines, stranding machine from Pourtier France, SKET Germany, Caballe Spain, 220KV and 35KV production line plus SIKORA X – RAY 8000 on-line eccentricity measuring unit from Germany
2.Complete certification system
We have gotten ISO 9001, ISO 14001, OHSAS 18001. Plant passed TUV, VDE, UL, CE, SAA, BS etc. certificate.
3.Perfect Production system
Our products cover LV power cable, MV power cable, HV&EHV power cable, ABC cables, ACSR/AAC/AAAC/ACAR/OPGW ,submarine cable, control cable, instrumentation cable, building wire, flexible rubber cable, fire rated cable, renewable cable, solar cable, industrial cable, Lan cable, coaxial cable etc.
4.Perfect Sales service system
We can offer the OEM/ODM service, Multiple products, Skilled Export sale engineer team, Reasonable price, Reliable quality, Friendly service.

Get a quote