The thermocouple compensation cables can also be termed as instrumentation cables, since they are used for process temperature measurement. The construction is similar to pair instrumentation cable but the conductor material is different. Thermocouples are used in processes to sense temperature and is connected to the pyrometers for indication and control. The thermocouple and pyrometer are electrically conducted by thermocouple extension cables / thermocouple compensating cables. The conductors used for these thermocouple cables are required to have similar thermo-electric (emf) properties as that of the thermocouple used for sensing the temperature.
Our mill mainly manufacture type KX,,EX,JX,TX,SC/RC,KCA,KCB compensating wire for thermocouple, and they are used in temperature measurement instruments and cables. Our thermocouple compensating products are all made abiding by GB/T 4990-2010 ‘Alloy wires of extension and compensating cables for thermocouples’ (Chinese National Standard), and also IEC584-3 ‘Thermocouple part 3-compensating wire’ (International standard).
The representing of the comp. wire: thermocouple code+C/X , e.g. SC, KX
X: Short for extension, means that the compensation wire’s alloy is as the same as the the alloy of the thermocouple
C: Short for compensation, means that the compensation wire’s alloy has similar characters with the thermocouple’s alloy in a certain temperature range.

Thermocouple Code Comp. Type Comp. Wire Name Positive Negative
Name Code Name Code
S SC copper-constantan 0.6 copper SPC constantan 0.6 SNC
R RC copper-constantan 0.6 copper RPC constantan 0.6 RNC
K KCA Iron-constantan22 Iron KPCA constantan22 KNCA
K KCB copper-constantan 40 copper KPCB constantan 40 KNCB
K KX Chromel10-NiSi3 Chromel10 KPX NiSi3 KNX
N NC Iron-constantan 18 Iron NPC constantan 18 NNC
N NX NiCr14Si-NiSi4Mg NiCr14Si NPX NiSi4Mg NNX
E EX NiCr10-Constantan45 NiCr10 EPX Constantan45 ENX
J JX Iron-constantan 45 Iron JPX constantan 45 JNX
T TX copper-constantan 45 copper TPX constantan 45 TNX

1. Chemical Composition

Material Chemical composition (%)
Ni Cr Si Mn Al
KP(Chromel) 90 10
KN(Alumel) 95 1-2 0.5-1.5 1-1.5

2. Physical properties and Mechnical properties

Material Density(g/cm3) Melting point(ºC) Tensile Strength(Mpa) Volume resistivity(μΩ.cm) Elongation rate (%)
KP(Chromel) 8.5 1427 >490 70.6(20ºC) >10
KN(Alumel) 8.6 1399 >390 29.4(20ºC) >15

3. EMF Value range at different temperature

Material EMF value Vs Pt(μV)
100ºC 200ºC 300ºC 400ºC 500ºC 600ºC
KP(Chromel) 2816~2896 5938~6018 9298~9378 12729~12821 16156~16266 19532~19676
KN(Alumel) 1218~1262 2140~2180 2849~2893 3600~3644 4403~4463 5271~5331
EMF value Vs Pt(μV)
700ºC 800ºC 900ºC 1000ºC 1100ºC
22845~22999 26064~26246 29223~29411 32313~32525 35336~35548
6167~6247 7080~7160 7959~8059 8807~8907 9617~9737

Type K Extension Cable Chromel / Alumel Material FEP insulation

Specifications

1.Style:Extension Wire
2.Thermocouple copper wire
Thermocouple copper wire Classification
1. Thermocouple level (high temperature level). This type of thermocouple wire is mainly suitable for thermocouple type K, J, E, T, N and L and other high temperature detection instrument, temperature sensor, etc.
2. Compensating wire level (low temperature level). This type of thermocouple wire is mainly suitable for compensating cable and extension wire of various thermocouples of type S, R, B, K, E, J, T, N and L, heating cable, control cable and so on.

Thermocouple variety and index

Thermocouple Variety and Index
Variety Type Measurement Range(°C)
NiCr-NiSi K -200-1300
NiCr-CuNi E -200-900
Fe-CuNi J -40-750
Cu-CuNi T -200-350
NiCrSi-NiSi N -200-1300
NiCr-AuFe0.07 NiCr-AuFe0.07 -270-0

3 . Dimensions and Tolerance of Fiberglass Insulated Thermocouple Wire

Dimensions / Tolerance mm ) : 4.0+-0.25

Color code & initial calibration tolerances for thermocouple wire:

Thermocouple Type ANSI Color Code Initial Calibration Tolerances
Wire Alloys Calibration +/-
Conductor
Jacket Temperature Range Standard
Limits
Special
Limits
CHROMEL(+) vs.
ALUMEL(-)
K Yellow/Red Brown -200°C to -110°C
-110°C to 0°C
0°C to +285°C
285°C to +1250°C
± 2%
±2.2°C
±2.2°C
± .75%
±1.1°C
± .4%

Color Code & Initial Calibration Tolerance for Extension Wire:

Extension type ANSI Color Code Initial Calibration Tolerances
Wire Alloys Calibration +/-
Conductor
Jacket Temperature Range Standard
Limits
Special
Limits
Iron (+) vs. Constantan(-) JX White/Red Black 0°C to +200°C ±2.2°C ±1.1°C
CHROMEL (+) vs. ALUMEL (-) KX Yellow/Red Yellow 0°C to +200°C ±2.2°C ±1.1°C
Copper(+) vs. Constantan(-) TX Blue/Red Blue -60°C to +100°C ±1.1°C ± .5°C
CHROMEL(+) vs. Constantan(-) EX Purple/Red Purple 0°C to +200°C ±1.7°C ±1.1°C

PVC-PVC Physical Properties:

Characteristics Insulation Jacket
Abrasion Resistance Good Good
Cut Through Resistance Good Good
Moisture Resistance Excellent Excellent
Solder Iron Resistance Poor Poor
Service Temperature 105ºC continuous
150ºC single
105ºC continuous
150ºC single
Flame Test Self-extinguishing Self-extinguishing

——Our Feature——

1.Imported equipment with experienced technical team
We have three plant and has 3048 employees which have 206 engineers. Plant has a series of imported production lines including Niehoff copper drawing lines, Troster Germany and Maillefer Finland 500KV VCV lines, stranding machine from Pourtier France, SKET Germany, Caballe Spain, 220KV and 35KV production line plus SIKORA X – RAY 8000 on-line eccentricity measuring unit from Germany
2.Complete certification system
We have gotten ISO 9001, ISO 14001, OHSAS 18001. Plant passed TUV, VDE, UL, CE, SAA, BS etc. certificate.
3.Perfect Production system
Our products cover LV power cable, MV power cable, HV&EHV power cable, ABC cables, ACSR/AAC/AAAC/ACAR/OPGW ,submarine cable, control cable, instrumentation cable, building wire, flexible rubber cable, fire rated cable, renewable cable, solar cable, industrial cable, Lan cable, coaxial cable etc.
4.Perfect Sales service system
We can offer the OEM/ODM service, Multiple products, Skilled Export sale engineer team, Reasonable price, Reliable quality, Friendly service.

Get a quote