Description
Applications
For use on single phase and three phase primary underground distribution systems operating at 20kV phase to phase. Suitable for either direct burial or installation in ducts.
Construction
Copper concentrically stranded compressed conductor, triple single head extruded conductor shield, XLPE (cross-linked polyethylene) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE or PVC jacket.
Standards
· IEC60502-2 Specification for Extruded Dielectric Shielded Power Cables Rated 3 through 30Kv
· IEC60228 Specification for cable conductors
· AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV
· ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 – 46,000V
· ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
· ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Notes
· Ampacities are based on the NEC.
· Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105°C conductor, at an ambient temperature of 40°C.
· Buried Duct: Three cables per duct operating at 105°C conductor, 20°C ground ambient, earth ρ = 90, 100% load factor.
· Conduit in Air: Three cables per isolated conduit in air at 40°C; operating at 105°C conductor (NEC Table 310.73).
· Maximum conductor temperature: 90°C normal continuous, 130°C overload, 250°C short circuit.
| Conductor | Round copper stranding, Compacted, Class 2 | |
|---|---|---|
| Internal semiconductor over conductor | Extruded layer of Conductive Material | |
| XLPE insulation thickness, | mm | 4.5 |
| outer semiconductive over XLPE insulation | Separable layer of conductive material extruded | |
| Metal copper screen section | mm2 | 16 |
| Diameter of copper wire in metal screen | mm | 0.584 |
| Number of copper wire in metal screen | 60 | |
| Outer jacket thickness and material | mm | 2.4, Polyethylene, ST7, Red |
| UV resistant | Ultraviolet (UV) | |
| Dimensions | ||
| Conductor section | mm2 | 1×630 |
| Diameter of conductor | mm | 29.6 |
| Electric character | ||
| voltage phase to earth | KV | 12 |
| voltage phase to phase | Um (KV) | 20 |
| Pulse voltage | KV | 125 |
| Rated current (outdoor) | A | 1095 |
| DC resistance at 20 ° C | Ohm/km | 0.047 |
| Inductive reactance | Ohm/km | 0.090 |
| Capacitance | µf / Km | 0.614 |
| Operating temperature | . | |
| Maximum allowable temperature in continuous operation | °C | 90 |
| Maximum allowable temperature regime shorts | °C | 250 |
——Our Feature——
1.Imported equipment with experienced technical team
We have three plant and has 3048 employees which have 206 engineers. Plant has a series of imported production lines including Niehoff copper drawing lines, Troster Germany and Maillefer Finland 500KV VCV lines, stranding machine from Pourtier France, SKET Germany, Caballe Spain, 220KV and 35KV production line plus SIKORA X – RAY 8000 on-line eccentricity measuring unit from Germany
2.Complete certification system
We have gotten ISO 9001, ISO 14001, OHSAS 18001. Plant passed TUV, VDE, UL, CE, SAA, BS etc. certificate.
3.Perfect Production system
Our products cover LV power cable, MV power cable, HV&EHV power cable, ABC cables, ACSR/AAC/AAAC/ACAR/OPGW ,submarine cable, control cable, instrumentation cable, building wire, flexible rubber cable, fire rated cable, renewable cable, solar cable, industrial cable, Lan cable, coaxial cable etc.
4.Perfect Sales service system
We can offer the OEM/ODM service, Multiple products, Skilled Export sale engineer team, Reasonable price, Reliable quality, Friendly service.